10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.
These 10 free ND-ELEC-B questions are organized by exam domain, so you can see how each part of the North Dakota Class B Electrician Exam blueprint is tested. Reveal the answer and explanation under each question.
Domain 1: fundamental electricity
Question 1
Lights in one part of a house become unusually bright while lights elsewhere dim when 120-V appliances switch on. At the 120/240-V service, a qualified electrician records 240 V line to line but 88 V and 152 V line to neutral. The line-to-neutral readings shift with the loads. What fault best explains this pattern?
Show answer & explanation
Correct answer: C - An open or high-resistance service neutral
Domain 2: Laws, Rules, and Wiring Standards of North Dakota
Question 2
Four city-property owners request rewiring bids from a North Dakota Class B electrician whose contracting registration and insurance are current. None of the properties is a farmstead. Which job is within this license's authorized scope?
Show answer & explanation
Correct answer: B - A two-family dwelling in a city with 1,900 inhabitants
Domain 3: National Electrical Code
Question 3
A $4,800 dwelling-addition project has a properly filed startup wiring certificate. The job log records work starting August 2, approved new circuits first being used August 5, electrical work being completed August 12, and the addition being occupied August 20. Which entry starts North Dakota's 15-day period for submitting final certificate paperwork and the proper fee?
Show answer & explanation
Correct answer: A - August 5: first use of the installation
More ND-ELEC-B practice questions
Question 4
A North Dakota dwelling's kitchen, pantry, and dining-room receptacles are being laid out. All proposed small-appliance circuits are 20 A with No. 12 copper conductors and supply no lighting or other prohibited outlets. Which design uses the fewest circuits while meeting the state's circuit-count and countertop circuit-arrangement requirements?
Show answer & explanation
Correct answer: A - Three circuits total; alternate adjacent countertop receptacles between two of them.
Question 5
A new detached garage receives a 120/240-V feeder with two ungrounded conductors, an insulated neutral, and an equipment grounding conductor. Its grounding electrodes connect to the bonded equipment-grounding bar. The installer also leaves the neutral bonding screw in place, reasoning that this is the garage's first disconnect. With the feeder safely deenergized, which single correction is needed?
Show answer & explanation
Correct answer: D - Remove the neutral bonding screw; retain the equipment-grounding and electrode bonds.
Question 6
A homeowner requests 48-A charging from a new hardwired EVSE. The existing dedicated circuit has a 50-A breaker and No. 6 copper NM-B cable with a final allowable ampacity of 55 A. The EVSE listing permits a qualified installer to secure its maximum setting at either 40 A or 48 A. No load-management allowance applies. Which commissioning choice is permissible without replacing the cable?
Show answer & explanation
Correct answer: B - Retain the 50-A breaker and commission the EVSE for 40-A charging.
Question 7
In a new North Dakota kitchen, the refrigerator and its single receptacle are each 4 ft from the sink, with no intervening obstacles. The receptacle is on an individual 20-A branch circuit and labeled 'Refrigeration Equipment Only.' Select the protection requirements after applying the state's refrigeration exceptions.
Show answer & explanation
Correct answer: C - GFCI is required; AFCI may be omitted.
Question 8
For a new North Dakota dwelling, the applicable floor area is 1,800 square feet. There are three required small-appliance branch circuits and one required laundry branch circuit. Using the 2026 NEC standard method, what is the combined general-lighting, general-use-receptacle, small-appliance, and laundry load after applying the dwelling demand factor, before adding other appliances or heating?
Show answer & explanation
Correct answer: D - 5,310 VA
Question 9
Floodwater has entered an energized basement panel, and the sump pump has stopped. A qualified electrician has identified a dry, safely accessible upstream disconnect that isolates the panel's only electrical supply. People have been kept out of the flooded area. Which task takes priority?
Show answer & explanation
Correct answer: A - Deenergize the panel at the dry upstream disconnect.
Question 10
A listed residential condensing unit is marked 'Minimum Circuit Ampacity: 24 A' and 'Maximum Circuit Breaker: 40 A.' The proposed conductors have a final allowable ampacity of 30 A, and the specified breaker is a listed 40-A two-pole GFCI breaker. Equipment overload protection is provided, and all other installation requirements are satisfied. How should the conductor-and-breaker selection be evaluated?
Show answer & explanation
Correct answer: B - Accept it: conductor ampacity meets MCA, and the breaker meets the marked maximum.
That's 10 of 1,030
The full bank has 1,020 more ND-ELEC-B questions with explanations.